Sklep internetowy - APS SA

SHOP ONLINE

OFFER

The offered LV switchgears, type SIKUS 1600, depending on the configuration and equipment, are designed for quick and easy distribution of energy in buildings of varying power demand by low-power main switchboards (630A, 800A, 1000A, 1250A, 1600 A) and sub-switchgears or distribution switchgears or departmental switchboards with less power (160A, 250A, 400A, 630A) with different options of systems in the connecting devices: it is possible to make solid (the cheapest), plug, or folding development. The latest circuit breakers were used in these switchboards: pneumatic, type Sentron 3WL and compact, type Sentron 3VL.

Target sets of switchgears, the quantity and type of switchgear fields, are configured in our company according to customer needs, based on the schema and the parameters required by it, using a special software of SIEMENS, the program SIMARIS CFB. "

522_7

Basic technical parameters of switchgears SIKUS 1600:

  • Protection class: 1
  • Rated impulse voltage strength: Uimp up to 8kV 
  • Overvoltage category: IV 
  • Pollution degree: 3 
  • Rated insulation voltage: Uj: 1000 V 
  • Rated operational voltage: Ue: 400 V 
  • Rated frequency: 50/60 Hz 
  • Rated current (In) of the main busbars (3, 4-pole): In: to 1600 A 
  • Rated peak withstand current in main busbars (3, 4-pole): Ipk: 120 kA 
  • Rated short time withstand current in main busbars (3, 4-pole): Icw (1 s): up to 55kA 
  • Operating conditions: ambient temperature: 35 ° 
  • Operating conditions: the height of location: up to 2000 m 
  • Forms of internal separation: 1, 2b, or other 
  • Protection class: IP30, IP40, IP55 
  • Protection against mechanical damage (according to IEC62262 item 9.6) : IP30-IK08, IP40-IK10
  • Surface finish: elements of the frame, internal components: galvanized: min layer.: 20 um 
  • Surface finish: housing elements: powder coated in color: RAL7035 
  • Surface finish: elements of design: powder-coated in Blue Green Basic color
  • Maximum weight of field (62208 according to IEC cz.9.3, 9.4): 1200 KG 
  • Possible configuration of sets with fields: power supply, coupling, outlet, and universal (apparatus) 
  • Field height: 2000mm 
  • Field width: 350, 400, 600, 850, 1100 mm
  • Depth of field: 400, 600 mm 
  • Cornice height: 100 mm
  • Possibility of flexible adjustment of the internal field division to the needs 
  • Use as a circuit-breakers of the input power line, 3WL SENTRON breakers 1600 A, or compact switches, type: SENTRON 3VL power up to 630 
  • Use as a circuit-breakers of outflows, branches of LV line of compact circuit breakers: SENTRON 3VL from16A to 630 (with thermomagnetic trigger) or from 63A to 630A  (with electronic trigger), 
  • Use as a circuit-breakers of power cable outlets of end users of low voltage power lines - fuse disconnectors, type: 3NJ4 (permanent development) or 3NJ6 (plug-in development) 
  • Possible remote communication through: power breakers Sentron 3WL/VL and module PROFIBUS DP 
  • Type tests in scope of: IEC 60439-1/2 and EN 60439, VDE 0660 item 500, 600-1

 

522_8

 

Projekt współfinansowany przez Unię Europejską z Europejskiego Funduszu Rozwoju Regionalnego w ramach Regionalnego Programu Operacyjnego Województwa Podlaskiego na lata 2007-2013 oraz ze środków budżetu państwa

FUNDUSZE EUROPEJSKIE - DLA ROZWOJU WOJEWÓDZTWA PODLASKIEGO
Urząd Marszałkowski Województwa Podlaskiego - Instytucja Zarządzającą RPOWP

Powiązane pliki:

icon Sikus 1600 POLE ODP?YWOWE BETA 2000x350x600 (189.62 kB 2011-02-28 22:35:06)

ul. A. Mickiewicza 95F 15-257 Białystok
tel. +48 (85)74 83 400
fax: +48 (85) 74 83 419